Home › Tools › Welder Power Calculator
Welder Power Calculator: Generator, Breaker, Wire and Extension Cord
Enter your welder's input amps, supply voltage and duty cycle. You get a generator size range, a breaker size, branch wire gauge and extension cord gauge by length, with the assumptions and sources shown. It is a planning aid, so check your welder's manual and local code.
How to use it
- Find the rated input amps on the welder's data plate or in the manual's specifications. It is usually labeled I1 or I1max, and it is listed separately for 120 V and 240 V.
- Enter the voltage and the duty cycle printed with the rating.
- If you only know the output amps, switch to the estimate mode. It uses the IEC load-voltage formula and an efficiency you can change.
- Read the generator range, breaker, branch wire and a cord table. Enter other tools if they will run on the same generator.
Worked examples from maker manuals
| Welder | Input | Generator (running) | Breaker / wire to it | Cord at 3% drop |
|---|---|---|---|---|
| ESAB Rebel EMP 215ic, 230 V, 30 A max MIG input (ESAB manual 0463 789 001) | 230 V × 30 A = 6,900 VA | 8,000 to 11,100 W | 30 A / 10 AWG | 25 ft: 8 AWG, 50 ft: 8 AWG, 100 ft: 8 AWG |
| Miller Multimatic 235, 240 V, 31.2 A rated max supply current (Miller OM-283935) | 240 V × 31.2 A = 7,488 VA | 8,700 to 12,000 W | 35 A / 8 AWG | 25 ft: 8 AWG, 50 ft: 8 AWG, 100 ft: 8 AWG |
Examples assume 100% duty, the most conservative case. The makers' own generator recommendations were 8,000 W (ESAB) and 12,000 W (Miller).
Affiliate disclosure: as an Amazon Associate, CanItBeWelded.com earns from qualifying purchases, at no extra cost to you. These links are searches, not endorsements of a specific product.
Assumptions and method
- Generator watts. Welder VA = volts × rated input amps. The range shown runs from the ESAB ratio (8,000 W ÷ 6,900 VA = 1.16) to the Miller ratio (12,000 W ÷ 7,488 VA = 1.60), plus any other tools you enter. Miller's generator guide says to limit the load to 90% of the generator's output, which is the VA ÷ 0.9 line. These are two makers' published recommendations, not a universal rule.
- Surge. Equal to the running figure plus the extra starting watts you enter for other tools. We found no welder maker that publishes a separate surge multiplier.
- Breaker. Smallest standard size (NEC 240.6(A)) at or above rated input amps. The NEC 630.12 ceiling is 200% of rated input and 200% of the conductor ampacity, whichever is lower, shown only as a maximum.
- Branch wire. Copper, 60 °C column of NEC Table 310.16. Minimum conductor ampacity = input amps × the NEC 630.11(A) duty-cycle multiplier. The conservative wire is sized to carry the suggested breaker.
- Extension cord. The cord must carry the full rated input amps, using the lower, 3-conductor column (Column A) of NEC Table 400.5(A)(1). Voltage drop = 2 × length × resistance per foot × amps, using NEC Chapter 9 Table 8 resistance for uncoated stranded copper at 75 °C, against the drop limit you pick.
- Estimate mode. Input amps = output amps × conventional load voltage ÷ (efficiency × supply volts). Load voltage is from IEC 60974-1: MIG 14 + 0.05 × amps, stick 20 + 0.04 × amps, TIG 10 + 0.04 × amps. The 75% efficiency default is our assumption; use your welder's spec if you have it.
NEC Table 630.11(A): duty-cycle multipliers (arc welders, non-motor-generator)
| Duty cycle | Multiplier |
|---|---|
| 20% | 0.45 |
| 30% | 0.55 |
| 40% | 0.63 |
| 50% | 0.71 |
| 60% | 0.78 |
| 70% | 0.84 |
| 80% | 0.89 |
| 90% | 0.95 |
| 100% | 1.00 |
Copper branch wire used (NEC Table 310.16, 60 °C column)
| Wire | Ampacity |
|---|---|
| 14 AWG | 15 A |
| 12 AWG | 20 A |
| 10 AWG | 30 A |
| 8 AWG | 40 A |
| 6 AWG | 55 A |
| 4 AWG | 70 A |
| 3 AWG | 85 A |
| 2 AWG | 95 A |
| 1 AWG | 110 A |
Flexible cord used (NEC Table 400.5(A)(1), Column A, and Chapter 9 Table 8)
| Cord | Ampacity | Ohms per 1,000 ft |
|---|---|---|
| 14 AWG | 15 A | 3.14 |
| 12 AWG | 20 A | 1.98 |
| 10 AWG | 25 A | 1.24 |
| 8 AWG | 35 A | 0.778 |
| 6 AWG | 45 A | 0.491 |
| 4 AWG | 60 A | 0.308 |
| 2 AWG | 80 A | 0.194 |
Sources
- NFPA 70, National Electrical Code: 630.11(A), 630.12, Table 310.16, 240.6(A), Table 400.5(A)(1), Chapter 9 Table 8 (check the edition your area has adopted)
- Miller Electric, Generator Power Application Guide (176 712L, 2012): limit load to 90% of generator output; Millermatic 212 listed at 6,500 W running and starting
- Miller Multimatic 235 Owner's Manual OM-283935: rated maximum supply current 31.2 A; recommends a 12 kW or greater generator for maximum output
- ESAB Rebel EMP 215ic Instruction Manual 0463 789 001: 230 V primary current, 8 kW generator with AVR, maximum extension cord length
- IEC 60974-1, Arc welding equipment, conventional load voltage formulas
Related guides and tools
Frequently asked questions
What size generator do I need to run a welder?
Start from the welder's rated input: volts × input amps from the data plate or manual. A 240 V welder rated for 30 A input is 7,200 VA. Then add margin. Miller says to limit the load to 90% of the generator's output, and the two makers we checked recommend more: ESAB suggests an 8 kW generator for a welder whose 230 V input is 30 A (6,900 VA), and Miller recommends 12 kW or more for maximum output on a Multimatic 235 (240 V × 31.2 A = 7,488 VA). If you can run below the welder's maximum output, a smaller generator can work. Your welder's manual wins.
Do I need extra generator watts for surge?
Not for the welder itself in the sources we found. Miller's generator guide lists a Millermatic 212 MIG welder at the same 6,500 watts running and starting. Surge matters for motors like compressors and grinders on the same generator, so enter their extra starting watts in the calculator.
What size breaker does a welder need?
The usual choice is the smallest standard breaker at or above the welder's rated input amps, unless the manual names a size. NEC 630.12 allows overcurrent protection up to 200% of the rated input current, but that is a ceiling, not a target. Follow the welder's manual and your local code.
What wire gauge do I need for a 240 V welder circuit?
Wire is sized from the welder's rated input amps and its duty cycle (NEC 630.11 multipliers), then checked against the breaker. This page uses copper and the 60 °C column of NEC Table 310.16 and shows both the minimum conductor and a conservative wire sized to the breaker. An electrician should confirm the final wire, run length and installation.
What extension cord can I use with a welder?
The shortest and heaviest one you can. The cord has to carry the welder's full input amps, and long runs drop voltage. Some makers set a hard limit, for example the ESAB Rebel EMP 215ic manual lists a maximum recommended extension cord length of 25 ft at 120 V and 50 ft at 230 V. If the manual gives a limit, use it.
Can I run a 240 V welder on 120 V?
Only a dual-voltage welder, with the right plug or adapter, and the output is lower on 120 V. The ESAB Rebel EMP 215ic, for example, lists a setting range up to 130 A on 120 V (20 A breaker) and up to 235 A on 230 V.
Can I use this instead of an electrician?
No. It is a planning aid. Wiring, breakers and generator connections should be checked against the welder's manual and local code, and a licensed electrician should do or approve any permanent circuit.